UPS charger power supply AD-155W
Features :
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
Battery low and battery polarity protection
Cooling by free air convection
100% full load burn-in test
Fixed switching frequency at 45KHz
1 year warranty
SPECIFICATION
|
MODEL
|
AD-155A
|
AD-155B
|
AD-155C
|
OUTPUT
|
|
|
|
Output number
|
CH1
|
CH2
|
CH1
|
CH2
|
CH1
|
CH2
|
DC voltage
|
13.8V
|
13.3V
|
27.6V
|
27.1V
|
54V
|
53.5V
|
Rated Current
|
11.5A
|
0.5A
|
5.5A
|
0.5A
|
2.7A
|
0.2A
|
Current Range
|
0~11.5A
|
0-0.5A
|
0~5.5A
|
0-0.5A
|
0-2.7A
|
0-0.5A
|
Rated Power
|
151.55W
|
151.55W
|
156.5W
|
Ripple & Noise
|
150mVp-p
|
--------
|
150mVp-p
|
--------
|
240mVp-p
|
--------
|
Voltage Adj. Range
|
CH1:12~14.5V
|
CH1:24~29V
|
CH1:48-58V
|
Voltage Tolerance
|
±2.0%
|
--------
|
±1.0%
|
--------
|
±1.0%
|
--------
|
Line Regulation
|
±0.5%
|
--------
|
±0.5%
|
--------
|
±0.5%
|
--------
|
Load Regulation
|
±0.5%
|
--------
|
±0.5%
|
--------
|
±0.5%
|
--------
|
Setup, Rise Time
|
1000ms, 90ms/230VAC 2000ms, 90ms/115VAC at full load
|
Hold Up Time
|
24ms/230VAC 20ms/115VAC at full load
|
|
|
INPUT
|
|
Voltage Range
|
88~264VAC 47~63Hz; 124~370VDC
|
AC Current
|
2.5A/115VAC 1.5A/230VAC
|
Efficiency
|
80%
|
84%
|
84%
|
Inrush Current
|
Cold start 20A/115VAC 40A/230VAC
|
Leakage Current
|
<1mA /240VAC
|
SIZE
|
199*110*50mm weight: 0.57kg
|
PROTECTION
|
Over load CH1:105 ~ 150% Over-voltage: 115-135%
|
working temperature |
-10℃~+60℃ 20%-90%RH |
withstand voltage |
I/P-O/P:3KVAC 1minute I/P-FG:1.5KVAC 1minute O/P-PG:0.5KVAC 1minute |
EMC standard
|
GB9254,EN55022 Class A
|